Table of Contents
Understanding Power Transformers
Power transformers are essential components in electrical power systems, designed to transfer electrical energy between circuits through electromagnetic induction. They play a critical role in adjusting voltage levels to ensure the efficient long-distance transmission of electricity. This is particularly important in large-scale applications where voltage regulation can significantly impact overall system performance.
| Type | Rated capacity (KVA) | Voltage combination(KV) | No-load losses(W) | Load losses(W) | No-load current (%) | Short-circuit impedance (%) |
| SZ11-2000 | 2000 | 33,35/6.3,6.6,10.5,11 | 2300 | 19240 | 0.80 | 6.5 |
| SZ11-2500 | 2500 | 33,35/6.3,6.6,10.5,11 | 2720 | 20640 | 0.80 | 6.5 |
| SZ11-3150 | 3150 | 33,35/6.3,6.6,10.5,11 | 3230 | 24710 | 0.72 | 7.0 |
| SZ11-4000 | 4000 | 33,35/6.3,6.6,10.5,11 | 3870 | 29160 | 0.72 | 7.0 |
| SZ11-5000 | 5000 | 33,35/6.3,6.6,10.5,11 | 4640 | 34200 | 0.68 | 7.0 |
| SZ11-6300 | 6300 | 33,35/6.3,6.6,10.5,11 | 5630 | 36800 | 0.68 | 7.5 |
| SZ11-8000 | 8000 | 33,35/6.3,6.6,10.5,11 | 7870 | 40600 | 0.60 | 7.5 |
| SZ11-10000 | 10000 | 33,35/6.3,6.6,10.5,11 | 9280 | 48100 | 0.60 | 7.5 |
| SZ11-12500 | 12500 | 33,35/6.3,6.6,10.5,11 | 10940 | 56900 | 0.56 | 8.0 |
| SZ11-16000 | 16000 | 33,35/6.3,6.6,10.5,11 | 13170 | 70300 | 0.54 | 8.0 |
| SZ11-20000 | 20000 | 33,35/6.3,6.6,10.5,11 | 15570 | 82800 | 0.54 | 8.0 |

The capacity of a transformer is measured in kVA (kilo-volt-amperes), and one common size used in industrial settings is the 2500 kVA transformer. Such transformers are capable of handling substantial loads, making them ideal for various applications, including substations and large manufacturing plants. Their design enables them to operate efficiently while minimizing energy loss, which is crucial for maintaining cost-effectiveness.
High Cost Performance in China Factories
China has established itself as a global leader in the production of power transformers, offering high-quality products at competitive prices. Factories in China leverage advanced manufacturing techniques and economies of scale to deliver transformers that not only meet international standards but also provide excellent cost performance. This makes Chinese-made transformers an attractive option for businesses looking to balance quality and budget.

The 2500 kVA transformer produced by Chinese manufacturers often features durable construction and reliable performance, ensuring longevity and reduced maintenance costs. These transformers are designed to withstand harsh operating conditions, providing users with peace of mind regarding their investment. Additionally, the affordability of these transformers allows companies to allocate resources more effectively across their operations.
Advantages of Choosing a 2500 kVA Transformer
When selecting a power transformer, the 2500 kVA model stands out due to its versatility and capability to manage significant power loads. This transformer size is suitable for a wide range of applications, including commercial buildings, large factories, and even renewable energy projects. Its ability to handle heavy electrical demands makes it an essential asset for any organization looking to optimize its power distribution.
| SC(B)11 | Rated capacity (KVA) | Voltage combination(KV) | No-load losses(W) | Load losses(W) | No-load current (%) | Short-circuit impedance (%) |
| SC11-30 | 30 | 6,6.3,6.6,10,11/0.4 | 180 | 710 | 2.4 | 4.0 |
| SC11-50 | 50 | 6,6.3,6.6,10,11/0.4 | 250 | 1000 | 2.4 | 4.0 |
| SC11-80 | 80 | 6,6.3,6.6,10,11/0.4 | 340 | 1380 | 1.8 | 4.0 |
| SC11-100 | 100 | 6,6.3,6.6,10,11/0.4 | 360 | 1570 | 1.8 | 4.0 |
| SC11-125 | 125 | 6,6.3,6.6,10,11/0.4 | 420 | 1850 | 1.6 | 4.0 |
| SCB11-160 | 160 | 6,6.3,6.6,10,11/0.4 | 490 | 2130 | 1.6 | 4.0 |
| SCB11-200 | 200 | 6,6.3,6.6,10,11/0.4 | 560 | 2530 | 1.4 | 4.0 |
| SCB11-250 | 250 | 6,6.3,6.6,10,11/0.4 | 650 | 2760 | 1.4 | 4.0 |
| SCB11-315 | 315 | 6,6.3,6.6,10,11/0.4 | 790 | 3470 | 1.2 | 4.0 |
| SCB11-400 | 400 | 6,6.3,6.6,10,11/0.4 | 880 | 3990 | 1.2 | 4.0 |
| SCB11-500 | 500 | 6,6.3,6.6,10,11/0.4 | 1050 | 4880 | 1.2 | 4.0 |
| SCB11-630 | 630 | 6,6.3,6.6,10,11/0.4 | 1210 | 5880 | 1.0 | 4.0 |
| SCB11-630 | 630 | 6,6.3,6.6,10,11/0.4 | 1170 | 5960 | 1.0 | 6.0 |
| SCB11-800 | 800 | 6,6.3,6.6,10,11/0.4 | 1370 | 6960 | 1.0 | 6.0 |
| SCB11-1000 | 1000 | 6,6.3,6.6,10,11/0.4 | 1590 | 8130 | 1.0 | 6.0 |
| SCB11-1250 | 1250 | 6,6.3,6.6,10,11/0.4 | 1880 | 9690 | 1.0 | 6.0 |
| SCB11-1600 | 1600 | 6,6.3,6.6,10,11/0.4 | 2210 | 11730 | 1.0 | 6.0 |
| SCB11-2000 | 2000 | 6,6.3,6.6,10,11/0.4 | 2720 | 14450 | 0.8 | 6.0 |
| SCB11-2500 | 2500 | 6,6.3,6.6,10,11/0.4 | 3200 | 17170 | 0.8 | 6.0 |
Investing in a 2500 kVA transformer from a reputable factory in China not only ensures high performance but also contributes to lower operational costs. With superior energy efficiency and reduced energy loss, these transformers can lead to substantial savings over time. Moreover, the availability of customization options allows businesses to tailor the transformer specifications to their unique needs, further enhancing their operational efficiency and productivity.